Product Overview

The Ground Busbar 3x25 12Pole gathers twelve protective earth connections onto one tin-plated copper bar. A cabinet, a rack enclosure or a medical panel needs that whenever a dozen frames, doors and shields must reach the same reference point.
Every pole takes three conductors of up to 25 mm² under its own screw, so each bonding conductor gets a pole instead of being tied to the next device. The route from a frame to earth stays one joint long.
Technical Specifications
Figures as published. Read two lines with care: the cross-section is 3 mm by 25 mm, and the 25 mm² below is a conductor entry, not the bar.
| Item | Specification |
|---|---|
| Busbar Cross-Section | 3 mm × 25 mm, 75 mm² of copper |
| Bar Material | Tin-plated copper, C11000 grade |
| Conductivity | ≥ 58 MS/m, 100% IACS, the grade figure for C11000 * |
| Continuous Current | 200 A in free air * |
| Short-Time Rating | 1.5 kA for 1 s * |
| Poles | 12 |
| Conductor Entries | Three per pole, up to 25 mm² each, under its own screw |
| Ground Resistance, Per Connection | ≤ 0.1 Ω * |
| Pole Pitch | 18 mm, standard DIN module spacing |
| Screw | Galvanised steel as standard; CuZn37 brass on request |
| Screw Locking | Spring lock washer on every pole |
| Mounting | Insulated supports, or directly to the cabinet frame |
| Identification | Green-yellow marking at every connection point |
| Referenced Standards | IEC 60947-1 and IEC 60947-7-1 are the families buyers ask for; no product standard is quoted for this item, so confirm the one your project calls for * |
| Minimum Order | Set by the build; trial volumes can be discussed |
| Production Lead Time | 7 to 10 days standard, 15 to 20 days custom |
| Warranty | 12 to 24 months from the date of shipment |
| Quality System | ISO 9001 |
| Packing | Export cartons |
| Shipping Ports | Ningbo / Shanghai |
| Quote Within | One working day of receiving the drawing and quantity |
Core Advantages
Four things decide whether a grounding bar still measures the same after a few years.
One Bar Of 75 mm² Copper
A 3 mm by 25 mm solid copper bar carries the bonding current, shared by twelve poles.
Tin Plating Keeps The Joint Conductive
Bare copper and brass darken in humid cabinet air, and that dulled layer is what pushes joint resistance up. Tin at 3 to 5 microns covers the bar before it ships.
One Reference Point, Not A Chain
Each conductor lands on its own pole, so a shield has one route to earth, not a chain of them.
Twelve Poles On One Bar
Twelve connection points at 18 mm pitch replace a row of discrete terminals, so the bonding schedule fits the panel width you already have.
Centralized Ground Bar versus Daisy-Chained PE Terminals
The alternative on most panel schedules is a row of separate PE terminals wired one to the next. Where the fault current travels is the difference.
| Point Of Comparison | This Bar | Discrete PE Terminals |
|---|---|---|
| Route to earth | One joint from the conductor to the bar | Every link adds a joint before the frame reaches earth |
| Conductors per point | Three entries, each under its own screw | Usually one conductor per terminal |
| Path for a shield return | One pole, one route | Through every terminal in the chain |
| Surface in humid air | Tin at 3 to 5 microns, no cleaning routine | Plating wears at the screw face |
| Adding one more device | Use a spare pole | Extend the rail and re-route the link |
| Short-time rating published | 1.5 kA for 1 s | Set by each terminal, rarely published |
| Ordering | 12 poles standard; other pole counts to drawing | Fixed sizes |
Professional Production Process
Five stages, with plating thickness and hole positions written to the batch record.
Bar stock cut to length and deburred to the drawing.
Pole holes, conductor holes and end fixing holes punched and drilled, positions held to ±0.1 mm.
Electrolytic tin plating at 3 to 5 microns, or 5 to 8 where a thicker coating is called up.
Screws and their spring lock washers assembled one pole at a time.
Each batch released on coating thickness, hole position, thread condition and tightening torque.
Material & Surface Treatment Options
Two choices travel with the order.
Tin-Plated C11000 Copper
C11000 is the high-conductivity grade. Electrolytic tin at 3 to 5 microns is standard; the 5 to 8 micron option suits coastal plants and sulfide atmospheres.
Screws: Galvanised Steel Or CuZn37 Brass
Steel screws are standard and take the hardest clamping load. Where the air is damp or salty, CuZn37 brass is the better choice: non-magnetic, and close enough to copper to hold galvanic corrosion down.
Application Scenarios
Three places a twelve-pole ground bar earns its keep.
Data Centre PDU And Rack Bonding
Rack frames, PDU chassis and busbar enclosures land on one bar, not a chain of terminals - the arrangement data-hall bonding practice expects.
Medical And Precision Instrument Bonding
Equipotential bonding for treatment rooms and instrument benches, where brass screws keep ferromagnetic metal away from low-level measurement circuits.
Control Cabinets, MCC Panels And Solar Combiners
MCC and PLC panels, distribution boards and inverter grounding, wherever twelve protective earth points are needed on one compact bar.
Products Description
Q: What does 3x25 mean here, and how many conductors fit?
A: The bar measures 3 mm by 25 mm, 75 mm² of copper. Each of the twelve poles takes three conductors of up to 25 mm². The two 25s are different things; the drawing shows both.
Q: What is the continuous rating, and on what basis?
A: 200 A in free air is what this page publishes. A closed enclosure will read lower, so send the cabinet arrangement and the load schedule and we will confirm the figure for your assembly.
Q: Is 1.5 kA for one second enough for my installation?
A: That is the published short-time rating. What settles it is the prospective earth-fault current where the bar is installed
Q: The table gives 0.1 ohm per connection. Is that the bar's resistance?
A: It is the continuity limit for the bonded path - the number a commissioning test compares against - not a measured joint resistance. Ask us for the measured value and the test current if your specification needs a tighter figure.
Q: Which screws should I specify, and to what torque?
A: Galvanised steel covers most cabinets; brass suits coastal sites, humid rooms and instrumentation. Torque follows the screw size, which this page does not publish, so send the drawing and we will confirm size, torque and packing.


Hot Tags: ground busbar 3x25 12pole, China ground busbar 3x25 12pole manufacturers, suppliers, factory, Neutral Busbar 3x30 10Pole, Neutral Terminal 250A 16 To 50sqmm, Neutral Terminal 400A 25 To 70sqmm, Neutral Terminal 600A 35 To 95sqmm, Standalone Neutral Terminal 100A 10 To 35sqmm, Standalone Neutral Terminal 600A 35 To 95sqmm