Product Overview

The Neutral Terminal 400A 25–70sqmm is a heavy-duty neutral busbar terminal built for high-current three-phase four-wire systems. Accepting 25–70 mm² copper conductors, it delivers a low-impedance neutral connection in main distribution boards, generator output circuits, and industrial switchgear.
A massive copper conductor block and pressure-plate clamping keep contact resistance extremely low at full load, so the joint stays cool and stable even when sudden load surges hit the system - the exact condition where ordinary terminals overheat and melt.
Technical Specifications
|
Item |
Specification |
|
Rated Current |
400A |
|
Rated Insulation Voltage (Ui) |
690V / 1000V AC |
|
Rated Impulse Withstand (Uimp) |
8 kV |
|
Short-Time Withstand Current (Icw) |
4 kA / 1s |
|
Temperature Rise |
≤ 50K at rated current (IEC 60947-7-1) |
|
Main Conductor Range |
25–70 mm² (Cu) |
|
Branch Conductor Range |
16–50 mm² (Cu) |
|
Main / Branch Clamp Screw |
M8 / M6 hex socket |
|
Recommended Torque |
10–14 N·m (main) / 5–7 N·m (branch) |
|
Connection Type |
Screw clamp with pressure plate |
|
Conductor Type |
Solid, stranded, finely stranded (Class 5/6) copper |
Core Advantages
High Surge-Current Withstand
Short-time withstand of 4kA for 1 second absorbs the inrush from suddenly applied generator loads without contact deformation or welding.
Large-Area Copper Contact
Oversized copper block maximizes contact area, keeping contact resistance below 0.2 mΩ and heat generation minimal at 400A continuous current.
Pressure-Plate Clamping
Even clamping force across the conductor cross-section protects finely stranded cables from strand damage and keeps torque stable over years of thermal cycling.
Verified Thermal Margin
Temperature rise controlled within 50K at rated current per IEC 60947-7-1, providing a long-term safety margin for 24/7 industrial operation.
400A Neutral Terminal vs Ordinary Terminal Block
|
Comparison |
Neutral Terminal 400A |
Ordinary Terminal Block |
|
Surge Current Withstand |
4kA/1s tested |
No rating; risk of melting under inrush |
|
Conductor Range |
25–70 mm² |
Typically ≤ 16 mm² |
|
Contact Structure |
Large copper block + pressure plate |
Small contact point |
|
Temperature Rise |
≤ 50K at 400A |
Overheats at high continuous load |
|
Design Standard |
IEC 60947-7-1 |
General purpose |
Professional Production Process
Copper bar cutting → CNC precision punching → thread tapping → deburring & chamfering → surface plating → 100% torque and dielectric testing. Every batch passes withstand-voltage and resistance checks before packing.
Material & Surface Treatment Options
Conductor Body
High-purity T2 copper block for maximum conductivity
01
Plating
Tin plating standard; nickel or silver plating optional for corrosive environments
02
Screws & Pressure Plates
Steel with zinc plating, hex socket for controlled torque
03
Custom plating and laser marking available per project requirements.
04
Application Scenarios
Generator Output & Neutral Connections
Handles the sudden load steps of genset startup, where inrush currents reach several times rated value and weak joints quickly burn out.
Main Distribution Boards
Central neutral bar for 400A-class three-phase four-wire panels in commercial and industrial buildings.
PV / Energy Storage & Data Centers
Reliable neutral termination in AC combiner boxes and UPS distribution where continuity is critical.
Frequently Asked Questions
Q:What conductor sizes does it accept?
A:Main conductors 25–70 mm² copper; branch conductors 16–50 mm². Solid, stranded, and finely stranded Class 5/6 cables are all supported.
Q:Can it survive generator inrush currents?
A:Yes. It is short-time tested at 4kA for 1 second and temperature-rise tested at full 400A per IEC 60947-7-1, specifically for genset and heavy inrush applications.
Q:Do you support OEM/ODM?
A:Yes. Custom hole counts, fixing dimensions, plating, and laser marking are available from drawings, with sample testing supported before bulk orders.


Hot Tags: neutral terminal 400a 25 to 70sqmm, China neutral terminal 400a 25 to 70sqmm manufacturers, suppliers, factory, Neutral Busbar 3x30 10Pole, Neutral Terminal 250A 16 To 50sqmm, Neutral Terminal 400A 25 To 70sqmm, Neutral Terminal 600A 35 To 95sqmm, Standalone Neutral Terminal 100A 10 To 35sqmm, Standalone Neutral Terminal 600A 35 To 95sqmm