Product Overview

The Switch Terminal 400 Frame 8x16 turns the load side of a 400 A frame moulded case circuit breaker into eight independent branch circuits, each taking 4 to 16 mm² copper on its own M5 screw clamp.
Landing eight branch conductors on one large breaker usually ends in lugs stacked over the load studs - the layout that crowds the cabinet, runs hot at the joints and oxidises. This block replaces the stack with one stamped copper body bolted onto the breaker's M8 studs, so every circuit leaves through its own clamp.
Technical Specifications
The rows below carry this model's own published figures; asterisked rows at the foot are range-wide commercial terms.
| Item | Specification |
|---|---|
| Function | Eight-way extension block expanding one 400 A frame breaker connection into eight branch circuits |
| Frame Rating | 400 A, compatible with 3-pole and 4-pole MCCBs |
| Outlets | 8 output circuits on one body |
| Wire Range | 4 to 16 mm² copper per outlet |
| Current Per Outlet | 63 A with 16 mm² copper |
| Inlet Connection | M8 stud, direct bolt-on to the breaker's load terminal (10 to 14 N·m) |
| Outlet Connection | M5 screw clamp, direct compression type (2.5 to 3.5 N·m) |
| Conductor Bar | High-purity T2 copper, stamped in one piece |
| Finish | Thick electro-tin plating, oxidation-resistant contact faces |
| Interphase Barriers | PA66+GF30, UL94 V-0 flame-retardant grade |
| Pole Pitch | 18 mm, DIN standard spacing |
| Overall Length | Approximately 170 mm |
| Protection | IP20 touch-proof construction |
| Creepage | Exceeds IEC 60947-7-1 minimums for 690 V applications |
| Customization | Hole spacing, stud size and plating thickness produced to drawing; OEM and ODM available |
| MOQ* | 10 pieces |
| Lead Time* | 7 to 10 days standard; 15 to 20 days custom |
| Quality Guarantee* | 12 to 24 months, counted from the shipment date |
| Manufacturing Standard* | ISO 9001 quality management system |
| Delivery Ports* | Ningbo Port / Shanghai Port |
| Quote Turnaround* | Within 24 hours of receiving the enquiry |
* Rows marked with an asterisk are commercial terms shared across this breaker terminal range rather than values this model publishes. The datasheet issued with each quotation states the terms that apply to the order.
Core Advantages
Four answers to the failure modes of an eight-branch layout wired the old way.
One Stamped T2 Copper Body, Thickly Tin-Plated
The conductor path is stamped from a single sheet of high-purity T2 copper - no seams, no cast joints - and the thick tin plating keeps every contact face oxide-free through years of full-load heat cycling.
Eight Outlets Sharing The Load Evenly
Each circuit carries its rated 63 A at 16 mm² through an identical clamp geometry, so no point concentrates current; in continuous full-load service the temperature rise holds about 15% under the IEC 60947-7-1 limit.
Eight Circuits On The Breaker's Own Footprint
The 170 mm body mounts straight onto the breaker's M8 studs, so eight branch points appear without a busbar run, a terminal row or extra drilling - and fitters land one cable per clamp instead of dressing lugs onto a stud.
Barriers And Creepage Sized For Eight Poles
Factory-fitted PA66+GF30 barriers (UL94 V-0) separate every pole, extended creepage distances clear the IEC 60947-7-1 minimums for 690 V service, and IP20 touch-proof construction keeps fingers out of the denser live cluster.
One 8-Way Extension Block vs Stacked Lugs On The Breaker Stud
Both layouts start from the same breaker; they differ in how many hand-made joints sit between it and the eight branches.
| What Changes | This 8-Way Block | Stacked Lug Wiring |
|---|---|---|
| Conductor landing | One cable per clamp, no stacking | Up to four lug barrels squeezed onto one stud |
| Current path | Breaker stud to branch through one copper body | Every branch crosses a lug-to-lug or lug-to-stud interface |
| Heat at the joints | Load spread across eight identical clamps | Concentrated where the barrels overlap |
| Oxidation over time | Thick tin plating on every contact face | Interfaces live or die by the re-tightening rounds |
| Cabinet space | One 170 mm block in place of the lug stack | Stack depth plus the dressing room eight tails need |
| Assembly work | Bolt the block on, land eight cables | Crimp, stack and torque every lug separately |
Application Scenarios
Where eight 16 mm² branches leave one 400 A breaker, these are the cabinets it lands in.
Heavy Industrial Switchgear Lines
Panel builders fitting out 400 A feeder sections standardise on one block per breaker instead of engineering a busbar for every cabinet.
Motor Control Centers
MCC integrators derive eight motor or feeder taps from a single 400 A incomer without stacking lugs inside the wiring chamber.
Data Center Power Distribution
PDU assemblers pack more branches into shallow enclosures, where the barrier-protected 18 mm pitch keeps adjacent live parts apart.
Frequently Asked Questions
Q: Will it bolt onto the breakers we already build with?
A: It mounts on the M8 load studs of standard 400-frame MCCB layouts. Send the breaker model with your enquiry and the stud pattern is checked against the terminal drawing before the order is placed.
Q: How does it hold temperature rise at full load?
A: Eight identical clamps share the current, each rated 63 A at 16 mm² copper, and the one-piece T2 copper path keeps joint resistance low. Full-load rise sits about 15% under the IEC 60947-7-1 limit.
Q: What torque do the connections take?
A: The M8 inlet studs take 10 to 14 N·m and the M5 branch clamps take 2.5 to 3.5 N·m. Both bands are printed on the datasheet issued with the quotation, so the assembly line sets one habit.
Q: What terms does an order run on?
A: Orders start from 10 pieces; standard builds ship in seven to ten days and custom work in fifteen to twenty. Include the breaker model and cable schedule and the quotation returns within 24 hours.


Hot Tags: switch terminal 400 frame 8x16, China switch terminal 400 frame 8x16 manufacturers, suppliers, factory, MCB Matching Terminal 4x10, RCCB Matching Terminal 100 Type, Switch Terminal 400 Frame 2x25, Switch Terminal 400 Frame 3x16, Switch Terminal 400 Frame 4x16, Switch Terminal 400 Frame 8x16