Product Overview

Single Pole One Inlet Five Outlet brings one incoming conductor out to five numbered branch terminals, in a body small enough for a control box with no room to spare.
Its first job is to give the joints somewhere to live. A shallow enclosure seldom has a free run of rail, and the usual answer - a connector hanging on its conductors, or five joints made in mid-air - leaves live metal unsupported. This block fixes instead: a clip for 35 mm DIN rail, or a screw fixing to the backplate.
Technical Specifications
| Item | Specification |
|---|---|
| Configuration | 1 pole, 1 inlet / 5 outlets |
| Maximum Total Input Current | 125 A continuous duty, published on this page |
| Load Basis | 125 A is the continuous rating of the block as a whole, not a simultaneous load on each of the five outlets |
| Rated Voltage | 690 V AC |
| Inlet Wire Range | 10 mm² – 35 mm², solid or stranded copper |
| Outlet Wire Range | 1.5 mm² – 10 mm², solid or stranded copper |
| Inlet Screw | M6, tightened to 5 – 7 N·m |
| Outlet Screw | M4, tightened to 1.5 – 2.5 N·m |
| Conductor | Tin-plated copper alloy |
| Conductor Scope | A single-pole block carries one polarity only, one conductor per position. Tapping live and neutral therefore takes two blocks on the same circuit, and the protective earth stays on the earth bar |
| Housing | PA66, UL94 V-0 |
| Mounting | Two fixing methods, both published here: a clip for standard 35 mm DIN rail, and a screw fixing to the panel backplate for enclosures with no rail |
| Circuit Identification | Five numbered positions, one conductor entry each, with labelling space for the load name and custom circuit numbering |
| Footprint | Approximately 80 mm × 45 mm × 35 mm |
| Protection With Cover Closed | IP20 - solid objects 12.5 mm and larger are kept out, which is finger contact. Dust sealing is a separate claim and is not made here. The transparent cover is listed as optional, and no rating is published for the block without it |
| Operating Temperature | −40 °C to +105 °C |
| Customization | Circuit count across the series, labelling and fixing detail built to your drawing; OEM and ODM available for volume orders |
| MOQ | 10 pieces |
| Lead Time | 7 to 10 days standard; 15 to 20 days custom |
| Quality Guarantee | 12 to 24 months, counted from the shipment date |
| Manufacturing Standard | ISO 9001 quality management system |
| Packaging | 20 pieces to a carton |
| Delivery Ports | Ningbo Port / Shanghai Port |
| Quote Turnaround | Within 24 hours of receiving the drawing |
Core Advantages
Two Fixing Methods, Both Published
A rail clip and a screw fixing to the backplate are both standard, so a shallow box with no rail takes the same block as a rail-fed panel.
Five Positions Held By The Moulding
The outlets sit in one closed body, not on a strip the installer spaces out, so the gap between branches is set by the tool at every position.
A Footprint Sized For The Box
At roughly 80 by 45 by 35 mm the body is why this model sits beside the six- and eight-way versions: in a board too shallow for a longer block, it fits.
Closed, Finger-Safe, Labelled
With the optional cover shut the assembly is IP20 and fingers are kept out; without it no rating is published. Every outlet carries its own number and its own entry.
Mounted Distribution Block vs Loose Terminal Strip
The difference is less in how a screw grips a conductor than in what the joint is fixed to.
| What Changes | This Five-Way Block | A Loose Strip Or Loose Joint |
|---|---|---|
| Where it sits | Clipped to 35 mm DIN rail, or screwed to the backplate | Wherever the conductors happen to fall, usually unsupported |
| Live parts | Behind one closed PA66 moulding rated UL94 V-0 | Bare metal on a plastic strip, or a wrapped joint |
| Distance between positions | Fixed by the moulding at all five outlets | Set by the installer, then held by tape or by nothing |
| Through heat cycles | The clip and screw hold the block, the moulding holds the spacing | The strip relaxes and the tape dries out, so the spacing drifts |
| Touch protection | IP20 with the optional cover closed | Terminations left open, extra insulation needed |
| Adding a circuit later | An unused position, or a second block clipped alongside | The strip is cut and re-drilled |
| Tracing a circuit | Five numbered positions with labelling space | Found by tag, or by counting from the end |
| Landing two polarities | Two blocks, one per polarity, both fed from the same circuit | Mixed polarity along one strip, which is where the mistake starts |
Professional Production Process
Copper bar cut, terminal seats punched to the drawing, and the cut faces deburred so a conductor meets metal.
Degreased, then tin plated to the drawing thickness.
Bodies moulded in PA66, the rail clip and screw bosses formed in the same shot.
All five positions checked for full screw travel, electrical results logged per batch.
Material & Surface Treatment Options
Two choices decide how this block reads after a few years in a warm box.
The Compound Behind The V-0 Grade
The body is moulded in PA66 rated UL94 V-0: the specimen self-extinguishes once the flame is removed, so a fault arc inside the box does not keep the housing burning.
Tin On The Copper Face
Contact faces are a tin-plated copper alloy, which keeps the oxide film that bare copper builds up in a warm box off both the contact face and the screw thread.
Application Scenarios
Three settings this block is built for, all short on space.
Lighting Distribution Boards
One phase fanned out to five final circuits - lighting rows, emergency lighting, a sign circuit - in a board that stays shallow.
Small Control And Equipment Boxes
Control boxes and machine panels taking a single feed out to five internal circuits, with the block screwed to the backplate.
Small Solar And Metering Enclosures
A short photovoltaic string set, or a meter box needing up to five circuits from one pole where a six- or eight-way block will not fit.
Frequently Asked Questions
Q: What is this block for?
A: It returns five branch circuits from one pole: compact lighting boards, small control boxes, short solar string sets and meter boxes needing up to five circuits.
Q: How is it fixed - does it need a DIN rail?
A: No. It clips to 35 mm DIN rail, and it can also be screwed through the body to the panel backplate. The second is what matters in a shallow box with no free rail.
Q: What are the ratings, and how much can the five outlets carry?
A: 125 A continuous for the block as a whole, on a 690 V AC rating, with the five branch circuits sharing that total. Inlet: 10–35 mm² at an M6 screw torqued to 5–7 N·m; outlets: 1.5–10 mm² at M4 torqued to 1.5–2.5 N·m.
Q: Is the block IP20 on its own, and what does UL94 V-0 cover?
A: IP20 is published with the transparent cover closed, and the cover is optional, so without it no rating applies. V-0 covers flame spread on a specimen only: it self-extinguishes once the flame is removed and drips nothing that keeps burning. Smoke tests are separate, with no report here.
Q: Can the block be produced to our own drawing and labelling?
A: Yes. Circuit count, labels and fixing detail are made to your drawing, and OEM or ODM is open on volume. Minimum order 10 pieces; standard builds 7 to 10 days, custom 15 to 20, with a quote inside 24 hours.


Hot Tags: single pole one inlet five outlet, China single pole one inlet five outlet manufacturers, suppliers, factory, distribution terminals, Single Pole One Inlet Eight Outlet, Single Pole One Inlet Six Outlet, Single Pole One Inlet Ten Outlet, Single Pole One Inlet Twelve Outlet, Two Inlet Four Outlet 35 To 70sqmm